Vibrating wire piezometer has started to give intermittent and variable readings
1. Introduction
If
a failure of any vibrating wire transducer or the electrical cable is
suspected, the following steps can be followed. The transducers
themselves are sealed and cannot be opened for inspection. The
“Troubleshooting Flowchart” (below) should also be followed if any
instrument failures are suspected.
2. Troubleshooting steps
The steps below and the Troubleshooting Flowchart are applicable generally to any vibrating wire instrument.
STEP 1
Before
any of the following steps are followed, the portable data logger
should be used to verify the stability of the reading and the audio
signal from the portable logger should be heard. An unstable (wildly
fluctuating) reading from a transducer or an unsteady audio signal are
both indications of possible problems with instruments or their related
electrical cables. If a portable data logger is giving faulty readings
or audio signals from all transducers, a faulty readout unit must be
suspected. Another readout unit should be used to check the
readings from the transducers and itmsoil Instruments Ltd. should be
consulted about the faulty readout unit.
STEP 2
The
resistance across the two conductors of the electrical cable should be
checked. This can be done using a multimeter device across the two
exposed conductors if the cable has not been connected to a terminal
cabinet, or can be done just as easily across the two conductors if the
instrument has been connected to such a terminal (or datalogger). The
resistance across the two conductors should be approximately of the
order of 120Ω to 180Ω. The majority of this resistance will come from
the transducer (say approximately 130Ω). Before proceeding to Steps 3
and 4, the continuity should be checked between conductors and earthing
screen of the electrical cable. If a continuity exists, a damaged cable
is confirmed.
STEP 3
If
the resistance across the two conductors is much higher than the values
quoted in “STEP 1” (or is infinite), a severed cable must be suspected.
STEP 4
If
the resistance across the two conductors is much lower than the values
quoted in “STEP 1” (say 80Ω or less) it is likely that cable damage has
occurred causing a short in the circuit.
STEP 5
If
the resistance is within the values quoted in “STEP 1” (i.e. 120Ω to
180Ω), AND no continuity exists between conductor and earth screen and
on checking the reading from the transducer, it proves to be still
unstable or wildly fluctuating, it must be assumed that the integrity of
the circuit is good. A faulty transducer could be suspected if
neighbouring construction activities do not account for the anomaly.
itmsoil Instruments Ltd. should be consulted. If the point at which the
cable is damaged is found, the cable can then be spliced in accordance
with recommended procedures.
Troubleshooting flowchart